LonWorks gateway
BACnet gateway
The Building Management System provides various control functions to integratedly manage the building air
conditioning system. These modules make it easy to control and manage various system equipment as well as the
air conditioners to offer efcient and economical operating environment.
Unitive and Various
BACnet gateway
Unitive & Various Building Management Module
• Interface for BACnet management system
• Maximum 256 indoor units plus ERVs support with a
maximum of 80 interface modules
• Combinational use of BACnet and S-NET 3/ S-NET Mini
• Includes DMS 2 functions
Ethemet
Ethemet
BACnet BMS
RS485
Connection
• On/Off control
• Operation mode
• Temperature setting
• Fan speed/direction
• ERV operation mode
• ERV fan speed
• Filter alarm reset
• User control restriction
• Operation mode lock
• Set temperature limit
• Emergency stop
• Output contact control
• On/Off control
• Operation mode
• Set/Room temperature
• Fan speed/direction
• ERV operation mode
• ERV fan speed
• Filter alarm
• User control restriction
• Thermo On/Off
• Power distribution
• Operation mode lock
• Set temperature limit
• In/Out contact state
• Emergency stop
• Error code
With the BMS control and monitoring function, BACnet gateway makes
it easy to control the air conditioning network in various ways. BACnet
gateway can control up to 256 indoor units, used in combination with S-NET
3 and S-NET Mini.
MIM-B17
*
(DMS-Bnet)
&RQWURO 0RQLWRULQJ
Control system
System Controller
Watt-hour Meter
Interface Module
2013 SAMSUNG System Air Conditioners
107106
Vue de la page 0
1 2 3 4 5 6 ... 22 23

Résumé du contenu

Page 1 - BACnet gateway

LonWorks gatewayBACnet gatewayThe Building Management System provides various control functions to integratedly manage the building air conditioning s

Page 2

Control Systems130 9,9,Building management system (2) AHU kit2. BACnet Gateway7) Object list󰞃 MIM-B17NInstanceNumberObject Object TypeObject NameUnit

Page 3 - 3) Description of parts

131 BUILDING MANAGEMENT SYSTEM (3) ERV (4) SIM (5) On/Off Controller (6) Interface module (Outdoor unit)InstanceNumberObject Object TypeObject NameUni

Page 4

Control Systems132 9,9,Building management system (7) BACnet Gateway (8) Digital input / output2. BACnet Gateway7) Object list󰞃 MIM-B17NBACnet Gateway

Page 5 - 5) Wiring

133 BUILDING MANAGEMENT SYSTEM8) Checking BACnet communication through Wireshark(1) Who-is (I-Am)• After device instance numbers have been automatica

Page 6

Control Systems134 9,9,Building management system2. BACnet Gateway8) Checking BACnet communication through Wireshark(3) ReadPropertyMultiple• Object_M

Page 7 - Wiring distance

135 BUILDING MANAGEMENT SYSTEM(5) Subscribe COV(6) COV NotificationRequestResponseNotificationResponse

Page 8

Control Systems136 9,9,Building management systemObject Type Support DescriptionAnalog Input[Indoor temperature], [Lower limit temperature], [Upper l

Page 9 - 7) Object list

137 BUILDING MANAGEMENT SYSTEM10) Property support specification(1) Device propertyProperty identifier Property dataCheck codeSupportDMS21 Object iden

Page 10 - Building management system

Control Systems138 9,9,Building management system2. BACnet Gateway10) Property support specification(2) Analog Input Property󰞄 MIM-B17NProperty identi

Page 11 - (5) On/Off Controller

139 BUILDING MANAGEMENT SYSTEM(3) Analog output propertyProperty identifier Property dataCheck codeSupportDMS21 Object identifier BACnetObjectIdentifi

Page 12

Control Systems122 9,9,Building management system• For BACnet protocol system Support DMS2 control function at the same time.(Unit : mm)DMS-Bnet2. BA

Page 13 - (2) ReadPropertyMultiple

Control Systems140 9,9,Building management system2. BACnet Gateway10) Property support specification(4) Binary input property󰞄 MIM-B17NProperty identi

Page 14

141 BUILDING MANAGEMENT SYSTEM(5) Binary output propertyProperty identifier Property dataCheck codeSupportDMS21 Object identifier BACnetObjectIdentifi

Page 15 - (5) Subscribe COV

Control Systems142 9,9,Building management system2. BACnet Gateway10) Property support specification(6) Multi-state input property󰞄 MIM-B17NProperty i

Page 16

143 BUILDING MANAGEMENT SYSTEMProperty identifier Property dataCheck codeSupportDMS21 Object identifier BACnetObjectIdentifier R V2 Object name Charat

Page 17 - INTEGER O X

123 BUILDING MANAGEMENT SYSTEM①②③④ ⑤⑥ ⑦DMS-Bnet③②①3) Description of partsNoNameFunction①LCD display Displays current time or menu②Menu button Access t

Page 18

Control Systems124 9,9,Building management system(3) BottomName DescriptionDI terminal 1 Digital Input connection terminal, Channel 1~Channel 5DI term

Page 19 - (3) Analog output property

125 BUILDING MANAGEMENT SYSTEM4) Connection diagramFor power distributionOn/Off controllerPower lineR1-R2R1-R2R1-R2F1-F2F1-F2F1-F2Watt-hour meterElect

Page 20

Control Systems126 9,9,Building management system2. BACnet Gateway5) Wiring󰞃 MIM-B17NConnecting with outdoor unitF1 F2 R1 R2Outdoor unitOutdoor unitOu

Page 21 - (5) Binary output property

127 BUILDING MANAGEMENT SYSTEMConnecting with outdoor unit and on/off controllerWiring distanceMaximum 16 outdoor units123f Distance between BACnet Ga

Page 22

Control Systems128 9,9,Building management system• Click ‘Object ID’ from the ‘Object ID’ column. Detail information window will appear and detail

Page 23

129 BUILDING MANAGEMENT SYSTEMSingle indoor unit has following point list.InstanceNumberObject Object TypeObject NameUnit Status valueInactive ActiveT