LonWorks Gateway Setting (Continued)
No. NV Name NV Type Remarks
1 nviDigitalOut[6] SNVT_ switch Control Digital output of DMS
2 nviAllO SNVT_hvac_emerg Control all indoor unit / ERV OFF
3 nvoDigitalOut[6] SNVT_ switch Display Digital output status of DMS
4 nvoDigitalIn[8] SNVT_ switch Display Digital input status of DMS
5 nvoSystemLock SNVT_switch Display System Lock status of DMS
6 nvoDMSAlarm SNVT_ count
Display communication error of the sub
device connected to DMS
7 nvoSystemAlarm SNVT_ count
2. DMS system Objects
No. NV Name NV Type Remarks
1 nciSndHrtBt
SNVT_time_sec
SCPTmaxSendTime
Send Heartbeat
2 nciMinOutTm
SNVT_time_sec
SCPTminSendTime
Minimum Send Time
3 nciMinDeltaTemp
SNVT_temp_p
SCPTminDeltaTemp
Min. dierence before update
4 nciDelayStatrup
SNVT_time_sec
SCPTpwrupDelay
Delay time after a power-up
3. Configuration Properties
<Unused Network Variables>
The network variable listed below do exist within our XIF file. However, they are not
explained in this document. They are exclusively intended for internal testing purpose
and should not be used by a user.
nvlVolt
nvoVoltFb
SOL_DMS2&BAC&LW_IBIM_EN_32138A-10_EN_150617.indd 93 2015-06-18 오후 5:34:30