Samsung Electronics 4-12
4-7. Application Update using FTP
No Parts Procedure Remark
1 Common 1) Connect BACnet Gateway to PC with a crossover
lan cable.
2) Set IP to 192.168.0.250.
- You can connect all BACnet Gateway with
192.168.0.254.
3) Connect to BACnet Gateway with FTP.
- ftp://192.168.0.254/../../../dms
4) Copy the provided application folder to PC and
Rewrite it to the application folder in BACnet
Gateway
connected by FTP.
5) Push [Reset] button once.
BACnet Gateway_E_32400A(1)_1.indd 12 2010-05-17 �� 10:34:54