Trouble Shooting
Problem Check Explanation/Solution
The information of
indoor units/ERVs is
not displayed.
Has the tracking been
successfully executed?
Tracking should be executed to
get the information of all devices
belonging to DMS.
Is the DMS connected to the
centralized controller correctly?
Check the communication cable
between the DMS and the
centralized controller. Be careful to
deal with the communication cable
because it has polarity. Check the
centralized controller is turned on.
Is the centralized controller
connected to the interface
module correctly?
Check the power/communication
cable between the centralized
controller and the interface module.
Indoor units are out of
control.
Is LAN cable properly
connected?
Check the LAN cable and the LAN
indicator.
Are the indoor units connected
to the DMS correctly?
Check the power/RS 485
communication cable.
Is PEAK power management
mode in operation?
In PEAK power management
mode, ‘Turning on the indoor unit’
or ‘Changing operation mode to
Cool/Auto/Dry’ will be restricted.
Peak power control is
out of order.
Does the DMS communication
have any problem?
Check the DMS communicates with
the interface module. It is
impossible to control peak power
if the DMS does not function
properly.
Did you assign the indoor unit
in a group before PEAK power
management alarm level has
turned on?
If you have not assigned the indoor
unit in a group, indoor unit will not
be included in PEAK power
management even the alarm level
has turned on.